Catalogue values for Online UPS (V2)

Category Specification Bid Requirement (Allowed Values)
Generic Rating in KVA 1.0 KVA
Switching Technology IGBT-PWM
Input Voltage AC Single phase 160V - 260V 50Hz
Output Voltage AC Single phase 230V +/-1% 50 Hz
Warranty for UPS (Years) 5 Or higher
Battery/Backup Bank Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) With Battery
Type of Battery (hint: NA in case Battery not provided) SMF-VRLA conforming to JISC:8702(Pt.I,II&III), Stationary Lead Acid Batteries (with tubular positive plates) in monobloc container conforming to IS:13369:1992 latest
Backup time (Minutes) (hint: NA in case battery not provided) 60 Minutes, 120 Minutes, 180 Minutes
Minimum Guaranteed VAH 1600 X Per KVA X Per hour of backup time
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided 2, 3 Or higher
Installation and Commissioning or Service Installation and Commissioning ( Covered in the Scope of Supply) Provided
Performance / Functional Inbuilt isolation transformer With, Without
Overall Efficiency (%) >/=90% & <94% without Inbuilt isolation transformer, >/=94% without Inbuilt isolation transformer
Overload limit 20% Overload for minimum 10 minute, 20% Overload for minimum 5 minute, 50% Overload for minimum 1 minute, 50% Overload for minimum 3 seconds
Total Harmonic Distortion(THD) (%) 3% Maximum @ 100% Linear Load
Accessories Accessories Rack for Batteries, Cabling 6 meters ( input upto 3m and output upto 3m), Paralleling kit (Hot Standby Configuration), Paralleling kit for synchronizing (Parallel Redundant Load Sharing Configuration), SNMP Card ( with Suitable Software ) for communication, The UPS shall be complete with Trolley for battery bank,battery, Cables and connectors etc, NA
Salient Features Protection Protection for under voltage at battery terminal, Protection of Over voltage, Short Circuit & over load at UPS output terminal, Over temperature protection
Alarms and Indications Indicator for Mains presence, Indicator for Battery charging and discharging, Indicator for Output Over Load with Audible Alarm, Indicator for Low Battery Voltage with Audible Alarm, Alarm for Over temperature, Alarm for Low Battery
Additional Features Pure Sinewave AC Output, NA
Design / Construction Type of Design / Construction Floor Standing, Rack Mountable
Operating Conditions Minimum Operating Temperature 0, -5 Or lower
Maximum Operating Temperature 50 Or higher
Reports And Certification Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification OEM
Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand Yes
As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes (For UPS rating upto 10KVA)