Catalogue values for High Mast Lighting Tower for large area with LED Flood Lighting System

Category Specification Bid Requirement (Allowed Values)
GENERIC Height of High Mast Tower (in Meters) 16
Installation and commissioning (Installation and commissioning work at multiple locations shall follow as per the guidelines of State/Central Govt rules and regulations as applicable) Yes. Including Civil work at site, No
Onsite warranty (in Years) 2
High mast System No of sections 2
Effective length of each section (in m) 8.5
Material construction: The mast shall be manufactured using special steel plates, conforming to 355 gradeasper BSEN10 025
Bottom diameter (in mm) - Minimum 540
Plate thickness for Middle (in mm) - Minimum 4
Plate thickness for Bottom (in mm) - Minimum 5
No of longitudinal welds / section (in Nos) 1, 2
Diameter of base plate (in mm) - Minimum 740
Thickness of base plate (in mm) - Minimum 25
Wind Load Maximum Wind load 47 m/sec, 50 m/sec
Door Opening Size of opening and closing door at base compartment of high mast (in mm) - Minimum 1200 x 250
Junction Box Ingress protection for Junction Box i.e. IP Class (as per IS/IEC:60529:2001 latest) Test Report from Central Government lab/NABL/ILAC accrediated lab and report shall furnish to buyer on demand IP 65
No of core 3, 5
Cable category FR-LSH, 1
Size of cable (in Sq mm) 2.5
Conductor material shall be Copper
Winch The winch shall have provision for manual operation in case of failure of the motor Yes
Stainless Steel Wire Rope The breaking load of each rope shall be at full load as per the relevant standard >/=2400 Kg, >/=2250Kg
Electrical System, Cable and Cable Connections No. of cores 3, 5
Cable shall be Armoured, Unarmoured
Conudctor material shall be Copper, Aluminium
Cable Category 1
Incoming power cable from feeder panel to base compartment of mast and cable shall conforming to IS:7098 (Part 1):1988 latest
Feeder pillar Panel Feeder pillar panel for each mast Yes
Feeder panel shall be suitable for 415 V, 3 phase, 4 wire, 50 Hz, AC
The control panels shall be Stand mounted
Ingress protection for feeder pillar panel i.e IP Class (as per IS/IEC:60529:2001 latest).Test Report shall furnish from Central Government lab/NABL/ILAC accrediated lab to buyer on demand IP 65
It shall be fabricated out of 14 SWG CRCA sheet steel
Thickness of sheet (in mm) 2
The panels shall be given pre-treatment and powder coated and color shall be Grey
The stand shall be painted in Black color
Cable entry shall be at the Bottom
The panels shall have knock outs of the required cable
Laminated circuit diagram shall be pasted inside of the door
Feeder pillar shall have pad locking arrangement Yes
Earth terminal 12 mm dia. Bolts
Panel shall have a sloping cover to avoid accumulation of dust Yes
Panel shall be provided with incoming & outgoing MCCB / MCB of appropriate rating and in desired quantity depending on total no of circuits in use yes
Timer for automatic ON & OFF of lights with pilot lamps shall be provided Yes
Bus bars material Yes. Copper
No of Cores 3, 5
Size of cable (in Sq.mm) 2.5
Cable Shall be Armoured, Unarmoured
The conductor material shall be Copper
cable category 1
LED FLOOD LIGHT LUMINAIRE No. of Luminaires for each high mast lighting tower (in Nos) 8
LED Rating/System Wattage/Rated Power for each luminaire 200W
Luminaire System Efficacy (Lumen/watt) >/= 100 Lm/Watt
Ingress Protection (IP Rating) as per IS:10322 (Part 1):1982 latest IP65, IP66
Mounting brackets (included) Adjustable
Input operating Voltage range and frequency 90 to 300 Volts AC at 50Hz+/-2Hz
Rated voltage 230 V AC 50 Hz
Colour temperature 6000K (+/- 500K)
Optic lense material (UV stabilised) (Write NA for without optic lense supply) Poly carbonate lense
Operating temperature range -20 deg C to +50 deg C, -10 deg C to +50 deg C
The luminaire shall be protected against surges and transients( Internal) >/=5KV
The luminaire shall be protected against surges and transients of >/=10KV (External) Yes
Extruded silicon loop gasket shall be provided in the lantern body to ensure a weather proof seal between the UV Glass cover and the metal housing to exclude the entry of the dust,water,insects etc Yes
Number of electronic control gear per luminaire (power supplies) 1 No.
Length of ISI marked three core wire (shall be provided along with supply of material) 50 cm