Catalogue values for Power Generator - DG Set (up to 900 KVA)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
Power Generator INSTALLATION CONFIGURATIONS | Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) | Fixed (Power Generators are permanently installed)", Transportable (Skid Mounted) (Power Generators are not permanently installed)", Mobile (Trailer mounted) (Power Generators having an integral chassis fitted with wheels) " |
OUTPUT CAPACITY RATING/ PHASE | Nominal Rated Capacity (kVA) | 100 |
ENGINE | Rated Engine Power (kWm) | 100 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator + Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience, 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher |
Type of Engine cooling | Liquid Cooled | |
Type of governer | Electronic Or higher | |
Number of cylinders (nos) | 4, 6 | |
Rated RPM of Engine (RPM) | 1500 | |
Fuel | High Speed Diesel (HSD) | |
Starting voltage (volt) | 12, 24 | |
ALTERNATOR | Voltage Regulation Grade | VG 1, VG 2, VG 3 Or higher |
CONTROL PANEL | Control Panel | Manual Control Panel, AMF Control Panel |
TRAILER | Trailer | Yes, NA for Fixed/Skid Mounted Power Generator |
Pay load of the Trailer | 0, 500, 1000, 2000 Or higher | |
Trailer Complying to CMVR act and Regulation | Yes, NA for Fixed/Skid Mounted Power Generator | |
SCOPE OF INSTALLATION | Installation | Without installation, with installation - inclusive in the scope of supply Or higher |
WARRANTY/SERVICES | Warranty on Complete power genertor/DG Set | 24, 36 Or higher |
Number of preventive maintenance visits offered in an year during warranty period (Supply of all consumables is the buyer's responsibilty)* | 1, 2, 3 | |
TEST REPORTS | Test report Available for (Test/approval) | Type Approval Certificate for the specified rating of the Power Generator from any of the designated agency authorized by CPCB, COP Certificate for engine, Type test report for Alternator as per IS:13364 (Part-1) latest / IS:13364 (Part-2) latest to prove conformity to the specifications |