Catalogue values for Power Generator - DG Set (up to 900 KVA)

Category Specification Bid Requirement (Allowed Values)
Power Generator INSTALLATION CONFIGURATIONS Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) Fixed (Power Generators are permanently installed)", Transportable (Skid Mounted) (Power Generators are not permanently installed)", Mobile (Trailer mounted) (Power Generators having an integral chassis fitted with wheels) "
OUTPUT CAPACITY RATING/ PHASE Nominal Rated Capacity (kVA) 100
ENGINE Rated Engine Power (kWm) 100 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator + Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience, 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher
Type of Engine cooling Liquid Cooled
Type of governer Electronic Or higher
Number of cylinders (nos) 4, 6
Rated RPM of Engine (RPM) 1500
Fuel High Speed Diesel (HSD)
Starting voltage (volt) 12, 24
ALTERNATOR Voltage Regulation Grade VG 1, VG 2, VG 3 Or higher
CONTROL PANEL Control Panel Manual Control Panel, AMF Control Panel
TRAILER Trailer Yes, NA for Fixed/Skid Mounted Power Generator
Pay load of the Trailer 0, 500, 1000, 2000 Or higher
Trailer Complying to CMVR act and Regulation Yes, NA for Fixed/Skid Mounted Power Generator
SCOPE OF INSTALLATION Installation Without installation, with installation - inclusive in the scope of supply Or higher
WARRANTY/SERVICES Warranty on Complete power genertor/DG Set 24, 36 Or higher
Number of preventive maintenance visits offered in an year during warranty period (Supply of all consumables is the buyer's responsibilty)* 1, 2, 3
TEST REPORTS Test report Available for (Test/approval) Type Approval Certificate for the specified rating of the Power Generator from any of the designated agency authorized by CPCB, COP Certificate for engine, Type test report for Alternator as per IS:13364 (Part-1) latest / IS:13364 (Part-2) latest to prove conformity to the specifications