Catalogue values for Online Ups Modular Type
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
GENERIC | Output power capacity including redudancy/Expandable (Rack facility) upto/Minimum backuptime (including redudancy) /Minimum VAH (VAH shall be calculate Battery voltage x Battery Ah x No. of batteries = Total VAH) | 150 KVA/240KVA/15 Minutes/61500 VAH, 150 KVA/240KVA/30 Minutes/123000 VAH, 150 KVA/240KVA/45 Minutes/184500 VAH, 150 KVA/250KVA/15 Minutes/61500 VAH, 150 KVA/250KVA/30 Minutes/123000 VAH, 150 KVA/250KVA/45 Minutes/184500 VAH, 160 KVA/240KVA/15 Minutes/65600 VAH, 160 KVA/240KVA/30 Minutes/131200 VAH, 160 KVA/240KVA/45 Minutes/196800 VAH, 160 KVA/250KVA/15 Minutes/61500 VAH, 160 KVA/250KVA/30 Minutes/123000 VAH, 160 KVA/250KVA/45 Minutes/184500 VAH, 60 KVA/120KVA/15 Minutes/24600 VAH, 60 KVA/120KVA/30 Minutes/49200 VAH, 60 KVA/120KVA/45 Minutes/73800 VAH, 4KVA/8KVA/6 minutes/1080 VAH, 8KVA/16KVA/6 minutes/2160 VAH, 16KVA/32KVA/6 minutes/4320 VAH, 100 KVA/200 KVA/15 Minutes/72000 VAH, 100 KVA / 150 KVA / 30 Minutes / 82000 VAH, 120 KVA / 125 KVA / 30 Minutes / 76800 VAH, 160 KVA / 240 KVA / 60 Minutes / 262400 VAH, 120 KVA / 240 KVA / 30 Minutes / 100800 VAH, 40KVA with 15/ 30 min backup 50KVA with 15/ 30 min backup 80KVA with 15/ 30 min backup, 60 KVA / 240 KVA / 30 Minutes / 50400 VAH, 60 KVA / 150 KVA / 60 Minutes / 103680 VAH, 10 KVA / 20 KVA / 30 Minutes / 15600 VAH, 15 KVA/ 30 KVA/ 30 Minutes/ 24000 VAH, 40 KVA/ 100 KVA/ 30 Minutes/ 20160 VAH |
Noise level | = 55 dB, = 65 dB, = 70 dB | |
INPUT | In put Voltage Range | 320 V to AC to 470 V AC 3 Phase, 340 V to AC to 470 V AC 3 Phase |
Input frequency range | 50 +/-6% Hz, 50 +/-10% Hz | |
Distortion (current) | < / = 3%, < / = 5% | |
OUTPUT | Output powr factor | >/= 0.90, >/=0.99 |
CONSTRUCTION | Minimum thickness (in mm) of Rack Enclosure for Modular UPS duly powder coated | 2.0, 1.2, others |
UPS enclosure's degree of protection as per IS:13947 (Part 1)/1993 latest | IP21, IP20 | |
Total Harmonic Distrotion (THD) for 100% linear load | < 3%, < 2% | |
Total Harmonic Distrotion (THD) for 100% non-linear load | < 5%, < 4% | |
Over all efficiency on rated full load of 0.8 PF (min.) AC output | >/=90%, >/=92%, >/=94%, >/=96% | |
Inverter efficiency on rated full load of 0.8 PF (min.) AC output | >/=95%, >/=96% | |
UPS shall withstand Over load capacity - 125% (Output with mains AC-AC) | for 5 Minutes (Minimum), for 10 Minutes (Minimum) | |
UPS shall withstand Over load capacity - 125% (Output in battery run DC-AC) | for 2 Minutes (Minimum), for 30 Seconds (Minimum) | |
BATTERY | Battery type | SMF VRLA, SMF VRLA, Modular Hot swappable Battery modules, Lithium Ion Battery [ as per IS 16046 (part 2)/ IEC 62133-2 and as per IEC 62485-5] |
Battery recharge time (after complete discharge to 90% charge) and charge rating: Battery recharge time to 90% charge after 100% DoD | 8 to 10 hours, 4 to 8 hours | |
Batteries shall supply with | With metal rack, With Modular cabinet having hot swappable battery | |
WARRANTY AND SERVICES | Warranty for Modular UPS (on site comprehensive warranty) (in years) | 3, 5, others |
Warranty for battery (replacement warranty) (in years) | 2, 3, 5, others | |
After sales and complaint service | within 24 hours, within 48 hours, Within 7 days | |
PAN India service support on 24 x 7 basis | Yes, No | |
AMC support available after 3 year warranty | Yes, No | |
Quarterly preventive maintenance | Yes, No | |
Manufacturer shall provide and support for installation, commissioning, spares, technical support all over India | Yes, No | |
Availability of spares in close proximity (Spares should be easily available close to the site) | Yes, No | |
CERTIFICATIONS | CE Certification and marking | Yes, No |
Damp Heat Test : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C,two cycles of (12+12) hours each 2007) | Yes, No | |
Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs | Yes, No | |
Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. | Yes, No | |