Catalogue values for Online Ups Modular Type

Category Specification Bid Requirement (Allowed Values)
GENERIC Output power capacity including redudancy/Expandable (Rack facility) upto/Minimum backuptime (including redudancy) /Minimum VAH (VAH shall be calculate Battery voltage x Battery Ah x No. of batteries = Total VAH) 150 KVA/240KVA/15 Minutes/61500 VAH, 150 KVA/240KVA/30 Minutes/123000 VAH, 150 KVA/240KVA/45 Minutes/184500 VAH, 150 KVA/250KVA/15 Minutes/61500 VAH, 150 KVA/250KVA/30 Minutes/123000 VAH, 150 KVA/250KVA/45 Minutes/184500 VAH, 160 KVA/240KVA/15 Minutes/65600 VAH, 160 KVA/240KVA/30 Minutes/131200 VAH, 160 KVA/240KVA/45 Minutes/196800 VAH, 160 KVA/250KVA/15 Minutes/61500 VAH, 160 KVA/250KVA/30 Minutes/123000 VAH, 160 KVA/250KVA/45 Minutes/184500 VAH, 60 KVA/120KVA/15 Minutes/24600 VAH, 60 KVA/120KVA/30 Minutes/49200 VAH, 60 KVA/120KVA/45 Minutes/73800 VAH, 4KVA/8KVA/6 minutes/1080 VAH, 8KVA/16KVA/6 minutes/2160 VAH, 16KVA/32KVA/6 minutes/4320 VAH, 100 KVA/200 KVA/15 Minutes/72000 VAH, 100 KVA / 150 KVA / 30 Minutes / 82000 VAH, 120 KVA / 125 KVA / 30 Minutes / 76800 VAH, 160 KVA / 240 KVA / 60 Minutes / 262400 VAH, 120 KVA / 240 KVA / 30 Minutes / 100800 VAH, 40KVA with 15/ 30 min backup 50KVA with 15/ 30 min backup 80KVA with 15/ 30 min backup, 60 KVA / 240 KVA / 30 Minutes / 50400 VAH, 60 KVA / 150 KVA / 60 Minutes / 103680 VAH, 10 KVA / 20 KVA / 30 Minutes / 15600 VAH, 15 KVA/ 30 KVA/ 30 Minutes/ 24000 VAH, 40 KVA/ 100 KVA/ 30 Minutes/ 20160 VAH
Noise level
INPUT In put Voltage Range 320 V to AC to 470 V AC 3 Phase, 340 V to AC to 470 V AC 3 Phase
Input frequency range 50 +/-6% Hz, 50 +/-10% Hz
Distortion (current) < / = 3%, < / = 5%
OUTPUT Output powr factor >/= 0.90, >/=0.99
CONSTRUCTION Minimum thickness (in mm) of Rack Enclosure for Modular UPS duly powder coated 2.0, 1.2, others
UPS enclosure's degree of protection as per IS:13947 (Part 1)/1993 latest IP21, IP20
Total Harmonic Distrotion (THD) for 100% linear load < 3%, < 2%
Total Harmonic Distrotion (THD) for 100% non-linear load < 5%, < 4%
Over all efficiency on rated full load of 0.8 PF (min.) AC output >/=90%, >/=92%, >/=94%, >/=96%
Inverter efficiency on rated full load of 0.8 PF (min.) AC output >/=95%, >/=96%
UPS shall withstand Over load capacity - 125% (Output with mains AC-AC) for 5 Minutes (Minimum), for 10 Minutes (Minimum)
UPS shall withstand Over load capacity - 125% (Output in battery run DC-AC) for 2 Minutes (Minimum), for 30 Seconds (Minimum)
BATTERY Battery type SMF VRLA, SMF VRLA, Modular Hot swappable Battery modules, Lithium Ion Battery [ as per IS 16046 (part 2)/ IEC 62133-2 and as per IEC 62485-5]
Battery recharge time (after complete discharge to 90% charge) and charge rating: Battery recharge time to 90% charge after 100% DoD 8 to 10 hours, 4 to 8 hours
Batteries shall supply with With metal rack, With Modular cabinet having hot swappable battery
WARRANTY AND SERVICES Warranty for Modular UPS (on site comprehensive warranty) (in years) 3, 5, others
Warranty for battery (replacement warranty) (in years) 2, 3, 5, others
After sales and complaint service within 24 hours, within 48 hours, Within 7 days
PAN India service support on 24 x 7 basis Yes, No
AMC support available after 3 year warranty Yes, No
Quarterly preventive maintenance Yes, No
Manufacturer shall provide and support for installation, commissioning, spares, technical support all over India Yes, No
Availability of spares in close proximity (Spares should be easily available close to the site) Yes, No
CERTIFICATIONS CE Certification and marking Yes, No
Damp Heat Test : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C,two cycles of (12+12) hours each 2007) Yes, No
Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes, No
Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes, No