Catalogue values for Online UPS (V2)

Category Specification Bid Requirement (Allowed Values)
Generic Rating in KVA 10.0 KVA
Switching Technology IGBT-PWM
Input Voltage AC Single phase 160V - 260V 50Hz, AC Three phase 300 V - 450V sinewave 50Hz
Output Voltage AC Single phase 230V +/-1% 50 Hz
Warranty for UPS (Years) 5 Or higher
Battery/Backup Bank Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) With Battery
Type of Battery (hint: NA in case Battery not provided) SMF-VRLA conforming to JISC:8702(Pt.I,II&III), Stationary Lead Acid Batteries (with tubular positive plates) in monobloc container conforming to IS:13369:1992 latest, Stationary Cells and Batteries, Lead Acid type (with tubular positive plates) conforming to IS:1651:1991 latest, Lithium Ion Battery [ as per IS 16046 (part 2)/ IEC 62133-2 and as per IEC 62485-5]
Backup time (Minutes) (hint: NA in case battery not provided) 60 Minutes
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided 2, 3 Or higher
Performance / Functional Inbuilt isolation transformer With, Without
Overall Efficiency (%) >/=80% & <90% with Inbuilt isolation transformer, >/=90% with Inbuilt isolation transformer, >/=90% & <94% without Inbuilt isolation transformer, >/=94% without Inbuilt isolation transformer
Overload limit 20% Overload for minimum 10 minute, 20% Overload for minimum 5 minute, 50% Overload for minimum 1 minute, 50% Overload for minimum 3 seconds
Accessories Accessories Rack for Batteries, Cabling 6 meters ( input upto 3m and output upto 3m), Paralleling kit (Hot Standby Configuration), Paralleling kit for synchronizing (Parallel Redundant Load Sharing Configuration), SNMP Card ( with Suitable Software ) for communication, The UPS shall be complete with Trolley for battery bank,battery, Cables and connectors etc, NA
Salient Features Alarms and Indications Indicator for Mains presence, Indicator for Battery charging and discharging, Indicator for Output Over Load with Audible Alarm, Indicator for Low Battery Voltage with Audible Alarm, Alarm for Over temperature, Alarm for Low Battery
Design / Construction Type of Design / Construction Floor Standing, Rack Mountable
Reports And Certification Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification NABL accredited lab