Catalogue values for Online UPS (V2)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
Generic | Rating in KVA | 40.0 KVA |
Switching Technology | IGBT-PWM | |
Input Voltage | AC Three phase 300 V - 450V sinewave 50Hz | |
Output Voltage | AC 3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz | |
Warranty for UPS (Years) | 2, 3, 4, 5 Or higher | |
Battery/Backup Bank | Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) | With Battery |
Type of Battery (hint: NA in case Battery not provided) | Lead Acid type (with tubular positive plates) conforming to IS:1651:1991 latest | |
Backup time (Minutes) (hint: NA in case battery not provided) | 30 Minutes | |
Minimum Guaranteed VAH | 1600 X Per KVA X Per hour of backup time | |
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided | 3 Or higher | |
Accessories with Battery | NA | |
Installation and Commissioning or Service | Installation and Commissioning ( Covered in the Scope of Supply) | Provided |
After sales service ( Turn Around Time) | NA | |
Preventive Maintenance ( Hint: Mention Timeline if provided, NA if not provided) | Monthly, Bi-Monthly, Quarterly, Half Yearly, Yearly, NA Or higher | |
Other Services provided | NA | |
Performance / Functional | Inbuilt isolation transformer | With |
Overall Efficiency (%) | >/=90% with Inbuilt isolation transformer | |
Overload limit | 20% Overload for minimum 10 minute, 50% Overload for minimum 3 seconds | |
Total Harmonic Distortion(THD) (%) | 3% Maximum @ 100% Linear Load | |
Other Functional Features | Crest factor on full non-linear load is not less than 3:1 | |
Accessories | Accessories | Cabling 6 meters ( input upto 3m and output upto 3m), Rack for Batteries |
Salient Features | Protection | Protection for under voltage at battery terminal, Protection of Over voltage, Short Circuit & over load at UPS output terminal, Over temperature protection |
Metering | Input Voltage | |
Alarms and Indications | Indicator for Mains presence | |
Additional Features | Pure Sinewave AC Output | |
Design / Construction | Type of Design / Construction | Floor Standing |
Enclosure (mm) | 1.2 mm Minimum Thickness of M.S. Sheet duly powder coated | |
Degree of Protection | IP21 Or higher | |
Other Constructional Features | UPS shall be free from workmanship defects, sharp edges, nicks, scratches, burst, etc. All fasteners shall be fixed properly. The equipment shall be complete with all parts and all parts shall be functional | |
Operating Conditions | Minimum Operating Temperature | 0, -5 Or lower |
Maximum Operating Temperature | 40, 45, 50 Or higher | |
Relative Humidity Non Condensing at 40 deg C | 90, 95 Or higher | |
Buyer Specific Requirement | Environmental Test Report Requirements | NA |
Battery Test Report | NA | |
Intended Applications | NA | |
Other Requirements | KW rating shall be 0.8 time of KVA rating | |
Reports And Certification | Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification | OEM |
Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand | Yes | |
As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable | Not applicable ( For UPS rating higher than 10KVA) | |