Catalogue values for Online UPS (V2)

Category Specification Bid Requirement (Allowed Values)
Generic Rating in KVA 40.0 KVA
Switching Technology IGBT-PWM
Input Voltage AC Three phase 300 V - 450V sinewave 50Hz
Output Voltage AC 3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz
Warranty for UPS (Years) 2, 3, 4, 5 Or higher
Battery/Backup Bank Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) With Battery
Type of Battery (hint: NA in case Battery not provided) Lead Acid type (with tubular positive plates) conforming to IS:1651:1991 latest
Backup time (Minutes) (hint: NA in case battery not provided) 30 Minutes
Minimum Guaranteed VAH 1600 X Per KVA X Per hour of backup time
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided 3 Or higher
Accessories with Battery NA
Installation and Commissioning or Service Installation and Commissioning ( Covered in the Scope of Supply) Provided
After sales service ( Turn Around Time) NA
Preventive Maintenance ( Hint: Mention Timeline if provided, NA if not provided) Monthly, Bi-Monthly, Quarterly, Half Yearly, Yearly, NA Or higher
Other Services provided NA
Performance / Functional Inbuilt isolation transformer With
Overall Efficiency (%) >/=90% with Inbuilt isolation transformer
Overload limit 20% Overload for minimum 10 minute, 50% Overload for minimum 3 seconds
Total Harmonic Distortion(THD) (%) 3% Maximum @ 100% Linear Load
Other Functional Features Crest factor on full non-linear load is not less than 3:1
Accessories Accessories Cabling 6 meters ( input upto 3m and output upto 3m), Rack for Batteries
Salient Features Protection Protection for under voltage at battery terminal, Protection of Over voltage, Short Circuit & over load at UPS output terminal, Over temperature protection
Metering Input Voltage
Alarms and Indications Indicator for Mains presence
Additional Features Pure Sinewave AC Output
Design / Construction Type of Design / Construction Floor Standing
Enclosure (mm) 1.2 mm Minimum Thickness of M.S. Sheet duly powder coated
Degree of Protection IP21 Or higher
Other Constructional Features UPS shall be free from workmanship defects, sharp edges, nicks, scratches, burst, etc. All fasteners shall be fixed properly. The equipment shall be complete with all parts and all parts shall be functional
Operating Conditions Minimum Operating Temperature 0, -5 Or lower
Maximum Operating Temperature 40, 45, 50 Or higher
Relative Humidity Non Condensing at 40 deg C 90, 95 Or higher
Buyer Specific Requirement Environmental Test Report Requirements NA
Battery Test Report NA
Intended Applications NA
Other Requirements KW rating shall be 0.8 time of KVA rating
Reports And Certification Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification OEM
Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand Yes
As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Not applicable ( For UPS rating higher than 10KVA)