Catalogue values for Online UPS (V2)

Category Specification Bid Requirement (Allowed Values)
Generic Rating in KVA 1.0 KVA
Switching Technology IGBT-PWM
Input Voltage AC Single phase 160V - 260V 50Hz, AC Three phase 300 V - 450V sinewave 50Hz
Output Voltage AC Single phase 230V +/-1% 50 Hz, AC 3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz, AC 3 phase 415V having a variable setting the range starting from 380 volt - variable upto to 415 volt.
Warranty for UPS (Years) 1, 2, 3, 4, 5 Or higher
Battery/Backup Bank Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) With Battery, Without Battery
Type of Battery (hint: NA in case Battery not provided) SMF-VRLA conforming to JISC:8702(Pt.I,II&III), Stationary Lead Acid Batteries (with tubular positive plates) in monobloc container conforming to IS:13369:1992 latest, Stationary Cells and Batteries, Lead Acid type (with tubular positive plates) conforming to IS:1651:1991 latest, NA, Lithium Ion Battery [ as per IS 16046 (part 2)/ IEC 62133-2 and as per IEC 62485-5]
Backup time (Minutes) (hint: NA in case battery not provided) 15 Minutes, 30 Minutes, 60 Minutes, 90 Minutes, 120 Minutes, 180 Minutes, 240 Minutes, NA
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided 1, 2, 3, NA Or higher
Performance / Functional Inbuilt isolation transformer With, Without
Overall Efficiency (%) >/=80% & <90% with Inbuilt isolation transformer, >/=90% with Inbuilt isolation transformer, >/=90% & <94% without Inbuilt isolation transformer, >/=94% without Inbuilt isolation transformer
Overload limit 20% Overload for minimum 10 minute, 20% Overload for minimum 5 minute, 50% Overload for minimum 1 minute, 50% Overload for minimum 3 seconds
Accessories Accessories Rack for Batteries, Cabling 6 meters ( input upto 3m and output upto 3m), Paralleling kit (Hot Standby Configuration), Paralleling kit for synchronizing (Parallel Redundant Load Sharing Configuration), SNMP Card ( with Suitable Software ) for communication, The UPS shall be complete with Trolley for battery bank,battery, Cables and connectors etc, NA
Design / Construction Type of Design / Construction Floor Standing, Rack Mountable