Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
Generic | Rating in KVA | 10.0 KVA |
Switching Technology | IGBT-PWM | |
Input Voltage | AC Three phase 300 V - 450V sinewave 50Hz | |
Output Voltage | AC Single phase 230V +/-1% 50 Hz | |
Warranty for UPS (Years) | 3, 4, 5 Or higher | |
Battery/Backup Bank | Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) | With Battery |
Type of Battery (hint: NA in case Battery not provided) | SMF-VRLA conforming to JISC:8702(Pt.I,II&III), Stationary Lead Acid Batteries (with tubular positive plates) in monobloc container conforming to IS:13369:1992 latest, Stationary Cells and Batteries, Lead Acid type (with tubular positive plates) conforming to IS:1651:1991 latest, Lithium Ion Battery [ as per IS 16046 (part 2)/ IEC 62133-2 and as per IEC 62485-5] | |
Backup time (Minutes) (hint: NA in case battery not provided) | 60 Minutes | |
Minimum Guaranteed VAH | 1600 X Per KVA X Per hour of backup time | |
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided | 2, 3 Or higher | |
Performance / Functional | Inbuilt isolation transformer | With |
Overall Efficiency (%) | >/=80% & <90% with Inbuilt isolation transformer | |
Overload limit | 20% Overload for minimum 10 minute, 20% Overload for minimum 5 minute, 50% Overload for minimum 1 minute, 50% Overload for minimum 3 seconds | |
Accessories | Accessories | Rack for Batteries |
Design / Construction | Type of Design / Construction | Floor Standing |
Enclosure (mm) | 1.2 mm Minimum Thickness of M.S. Sheet duly powder coated, 1.0 mm Minimum Thickness of M.S. Sheet duly powder coated | |
Operating Conditions | Maximum Operating Temperature | 40, 45, 50 Or higher |
Relative Humidity Non Condensing at 40 deg C | 90, 95 Or higher | |
Buyer Specific Requirement | Environmental Test Report Requirements | Damp Heat Test : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C, two cycles of (12+12) hours each 2007), Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs, Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs, NA |
Intended Applications | Critical Infrastructure, Network IT Equipment, Medical Equipment, Support for Data Centers, Network operating centers, Security operation centers, State and District centers, Command and Control center etc., across the Country to provide impetus to the e-Governance services e.g. Public food distribution, e Way bill, Counseling, e-Office, IVFRT etc., services under Digital India Programme, NA | |
Other Requirements | ROHS compliance, KW rating shall be 0.8 time of KVA rating | |
Reports And Certification | Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand | Yes |
As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable | Yes (For UPS rating upto 10KVA) | |