Catalogue values for Online UPS (V2)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
Generic | Rating in KVA | 2.0 KVA |
Switching Technology | IGBT-PWM | |
Input Voltage | AC Single phase 160V - 260V 50Hz | |
Output Voltage | AC Single phase 230V +/-1% 50 Hz | |
Warranty for UPS (Years) | 5 Or higher | |
Battery/Backup Bank | Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) | With Battery |
Type of Battery (hint: NA in case Battery not provided) | SMF-VRLA conforming to JISC:8702(Pt.I,II&III), Stationary Lead Acid Batteries (with tubular positive plates) in monobloc container conforming to IS:13369:1992 latest | |
Backup time (Minutes) (hint: NA in case battery not provided) | 60 Minutes, 90 Minutes, 120 Minutes | |
Minimum Guaranteed VAH | 1600 X Per KVA X Per hour of backup time | |
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided | 2, 3 Or higher | |
Installation and Commissioning or Service | Installation and Commissioning ( Covered in the Scope of Supply) | Provided |
Performance / Functional | Inbuilt isolation transformer | With, Without |
Overall Efficiency (%) | >/=90% with Inbuilt isolation transformer, >/=90% & <94% without Inbuilt isolation transformer | |
Overload limit | 20% Overload for minimum 10 minute, 20% Overload for minimum 5 minute, 50% Overload for minimum 1 minute, 50% Overload for minimum 3 seconds | |
Total Harmonic Distortion(THD) (%) | 3% Maximum @ 100% Linear Load | |
Accessories | Accessories | Rack for Batteries, Cabling 6 meters ( input upto 3m and output upto 3m), Paralleling kit (Hot Standby Configuration), Paralleling kit for synchronizing (Parallel Redundant Load Sharing Configuration), SNMP Card ( with Suitable Software ) for communication, The UPS shall be complete with Trolley for battery bank,battery, Cables and connectors etc, NA |
Salient Features | Protection | Protection for under voltage at battery terminal, Protection of Over voltage, Short Circuit & over load at UPS output terminal, Over temperature protection |
Alarms and Indications | Indicator for Mains presence, Indicator for Battery charging and discharging, Indicator for Output Over Load with Audible Alarm, Indicator for Low Battery Voltage with Audible Alarm, Alarm for Over temperature, Alarm for Low Battery | |
Additional Features | Pure Sinewave AC Output, NA | |
Design / Construction | Type of Design / Construction | Floor Standing, Rack Mountable |
Operating Conditions | Minimum Operating Temperature | 0, -5 Or lower |
Maximum Operating Temperature | 45, 50 Or higher | |
Buyer Specific Requirement | Battery Test Report | Type Test Report as per relevant governing specifications from Govt Lab/NABL accredited lab |
Intended Applications | Critical Infrastructure, Network IT Equipment, Medical Equipment, Support for Data Centers, Network operating centers, Security operation centers, State and District centers, Command and Control center etc., across the Country to provide impetus to the e-Governance services e.g. Public food distribution, e Way bill, Counseling, e-Office, IVFRT etc., services under Digital India Programme, NA | |
Other Requirements | ROHS compliance, KW rating shall be 0.8 time of KVA rating, NA | |
Reports And Certification | Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification | OEM |
Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand | Yes | |
As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable | Yes (For UPS rating upto 10KVA) | |