Catalogue values for XLPE Cable for Working Voltages up to and Including 1.1 KV as per IS 7098 (Part 1)

Category Specification Bid Requirement (Allowed Values)
STANDARDS Conformity of the specification for XLPE cable as per IS:7098 (Part 1): 1988 latest
Cables suitable for use in mines Yes, No
Cables suitable for use in low temperature applications No
GENERIC Classification of cables for improved fire performace category 01
Nominal Area of Conductor (in Sq mm) 300
Number of core (in Nos) 3.5
CONSTRUCTION Material of conductor Aluminium
Conductor material standard as per IS:8130:2013 latest
Type of inner sheath Thermoplastic
ARMOURING Type of cable Armoured cable
Material of armouring Aluminium flat strip
Type of armouring Single strip
MARKING ON CABLE Type of sequential marking on cable Screen printing on cable, Embossed on cable
PACKING AND MARKING Drum standard as per IS:10418 latest
CERTIFICATION Availability of type test report from Govt Lab/ NABL accredited LAB / ILAC accredited LAB Yes as per Cl.15 of IS:7098 Part 1, Yes as per Cl. 15.of IS:7098 Part 1 including mines cable requirements
Availability of Optional Test Reports Cold bend test for outer sheath, Cold impact test for outer sheath, Resistance test for Armour, Not applicable