Catalogue values for Line Interactive UPS with AVR (V2)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
GENERIC | Rating (in KVA) | 0.65, 0.8, 1.0, 1.5, 2.0, 3 Or higher |
Technology | MOSFET-PWM | |
Inverter Efficiency (%) | 70% or better Or higher | |
Minimum Guaranteed Battery Backup time (Minutes) on Full Load | 15, 30, 60, 90, 120, 180, 240 Or higher | |
Warranty for Line Interactive UPS | 3 Years, 4 Years, 5 Years Or higher | |
Battery/Backup Bank | Location of Battery | Outside the Enclosure of UPS |
Warranty for the battery from the date of delivery | 2 Years Or higher | |
CONSTRUCTIONAL | Enclosure | ABS |
Degree of protection | IP21, IP 20 Or higher | |
FEATURES | Rated Output (Volt) with Total Harmonic Distortion (%) | Single Phase Sinewave 230v AC 50Hz with Total Harmonic Distortion as <3% Or higher |
Input (Volt) | Single Phase AC (160-280V) | |
Salient Features | Maximum 10 milliseconds Switching over time | |
Variation in AVR output in AC mode (AVR Voltage regulation) | 230 Volts +/-9% | |
Protection | Under voltage Protection (Input Voltage <160 V) | |
BUYER SPECIFIC REQUIREMENT | Environmental Test Report Requirements | NA |
Any Other Requirements | As per Meity (Government of India) guidelines UPS shall have valid IS16242-Part 1 CRS certification | |
CERTIFICATION / TEST REPORT | Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification | Certificate of Govt.Lab/NABL/ILAC accredited for UPS Testing |
Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand | Yes | |