Catalogue values for XLPE Cable for Working Voltages up to and Including 1.1 KV as per IS 7098 (Part 1)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
STANDARDS | Conformity of the specification for XLPE cable | as per IS:7098 (Part 1): 1988 latest |
Cables suitable for use in mines | Yes | |
Cables suitable for use in low temperature applications | Yes | |
GENERIC | Classification of cables for improved fire performace category | C2 - FR-LSH |
Nominal Area of Conductor (in Sq mm) | 16 | |
Number of core (in Nos) | 4 | |
CONSTRUCTION | Material of conductor | Aluminium |
Conductor material standard | as per IS:8130:2013 latest | |
Construction of the conductor | Stranded and shaped | |
Colour of XLPE insulation | Red, Yellow, Blue, Black | |
Type of inner sheath | Thermoplastic | |
Additional requirement | NA | |
ARMOURING | Type of cable | Armoured cable |
Material of armouring | Galvanized round steel wire | |
Type of armouring | Single wire | |
Number of armouring wire / strip for each size of cable (in Nos) - Must declare (hint: for Unarmoured cables select '0') | 10 | |
OUTER SHEATH | Outer sheath standard | Conforming to IS:5831:1984 latest |
Type of outer sheath | PVC-ST2 | |
Colour of outer sheath | Black | |
MARKING ON CABLE | Manufacturer's identification on cable | as per Cl.17.1 of IS:7098 Part 1: latest |
Type of sequential marking on cable | Screen printing on cable | |
Cable identification | as per Cl.17.2 of IS:7098 Part 1: latest | |
Additional marking on Cable | NA | |
PACKING AND MARKING | Packing and marking | as per Cl.18.1 and 18.2 of IS:7098 Part 1: latest |
Cable wound on | ISI Marked Wooden drum | |
Drum standard | as per IS:10418 latest | |
Standard length of cable on drum (in m) | 500 | |
Marking on the drum | as per Cl.18.2 of IS:7098 Part 1: latest | |
CERTIFICATION | Availability of type test report from Govt Lab/ NABL accredited LAB / ILAC accredited LAB | Yes as per Cl.15 of IS:7098 Part 1 |
Availability of Optional Test Reports | Cold bend test for outer sheath, Cold impact test for outer sheath, Resistance test for Armour, Not applicable | |