Catalogue values for Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
STANDARDS | Energy efficiency level | 1 |
BEE Star Rating | 1 | |
Installation, Testing and Demonstration | No | |
Minimum warranty on receipt of stores (in Months) | 30 | |
Minimum warranty from the date of installation (in Months) | 24 | |
RATINGS | Nominal system voltage, HV ( in kV) | 11 |
Nominal system voltage, LV ( in V) | 415 | |
Standard ratings (in kVA) | 630 | |
Minimum basic insulation level (in kVP) | 75 | |
No load voltage ratios (in Volts) | 11000/433-250 | |
Highest system voltage for equipment (in kV) | 12 | |
Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 | |
CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
Conductor (Winding) material | Copper | |
Vector Group | Dyn-11 | |
Type of Mounting | Ground Mounted | |
Noise level at rated voltage and freqeuncy, Maximum (in dB) | 55 | |
TRANSFORMER TANK | Transformer tank cover construction | Non-sealed, Bolted |
Tank configuration with | With radiator fins | |
Material of transformer tank | Stainless steel | |
Minimum thickness of top and bottom material of transformer tank (in mm) | 6 | |
Minimum thickness of side material of transformer tank (in mm) | 4 | |
Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size), Brass (for upto 12 mm size), Electro Galvanized (for above 12 mm size), Hot Dip Galvanized (for above 12 mm size) | |
Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) | |
Provision of conservator | Yes , for Non sealed type with Plain tank construction | |
Painting | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Oil resistant paint |
Type of painting on External surface of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Polyurethane (finish coat) | |
TAP CHANGER | Winding tapped | HV |
No. of positions (in Nos.) | 7 | |
Voltage variation | +5% to -10% in steps of 2.5% for variation of HV | |
TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 4 Nos. (Conforming to IS:7421) | |
Suitable provision for adoption of cables of suitable size on LV side | No | |
Cable End Box on HV side | No | |
Cable End Box on LV side | Yes | |
MARKING | Material of rating plate | Anodized aluminium |
Marking method on rating plate | Engraved | |
Rating and terminal marking plates combined into one plate | Yes | |
OPTIONAL FITTINGS | Suitable rating lightning arrestors | HT Side, 1 No. per phase |
Bird guard | Yes | |
Terminal connectors | Yes | |
Oil temperature indicator and widning temperature indicator | Yes | |
Jacking pads | No | |
Buchholz relay | Yes | |
Magnetic oil level gauge with low oil level alarm contact | No | |
Non return valve | Yes | |
Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | Yes | |
Unidirectional flat rollers | Yes | |
Drain cum sampling valve | Yes with steel plug (for transformers upto 500 KVA) | |
Self protection / disconnection devices | On secondary side (as per IS/IEC:60947-2:2003 | |
Expulsion fuse as disconnection device | On Primay side (as per IS:9385 (Part 2):1980 | |
SERVICE CONDITION | Maximum altitude | <1000 m |
TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
Agreed for stage Inspection as required by buyer | Yes | |
SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | No |
Availability of test report for short circuit withstand test | No | |
Availability of test report for No load current at 112.5 % Voltage | Yes | |
Availability of test report for Paint adhesion test | No | |
BDV and moisture content of oil in the transformer | Yes for 1 No. | |
Other requirements | Losses and Impedance values as per Cl.7.8 and Table 6 of IS:1180 (Part 1):2014 latest, Limits of temeprature-rise as per Cl.7.10 of IS:1180 (Part 1):2014 latest | |