Catalogue values for Line Interactive UPS with AVR (V2)

Category Specification Bid Requirement (Allowed Values)
GENERIC Rating (in KVA) 0.65, 0.8, 1.0, 1.5, 2.0, 0.6, 3 Or higher
Technology MOSFET-PWM
Inverter Efficiency (%) 70% or better Or higher
Minimum Guaranteed Battery Backup time (Minutes) on Full Load 15, 30, 60, 90, 120, 180, 240 Or higher
Warranty for Line Interactive UPS 3 Years, 4 Years, 5 Years Or higher
Battery/Backup Bank Location of Battery Inside the Enclosure of UPS
Warranty for the battery from the date of delivery 2 Years Or higher
CONSTRUCTIONAL Enclosure ABS
Degree of protection IP21, IP 20 Or higher
FEATURES Rated Output (Volt) with Total Harmonic Distortion (%) Single Phase Quasi Sinewave 230 V AC 50 Hz with Total Harmonic Distortion as <=40%, Single Phase Sinewave 230v AC 50Hz with Total Harmonic Distortion as <3% Or higher
Input (Volt) Single Phase AC (160-280V)
Salient Features Maximum 10 milliseconds Switching over time, Load Power Factor >/=0.6, +/-10% Variation in output voltage in battery mode,
Variation in AVR output in AC mode (AVR Voltage regulation) 230 Volts +/-9%
Protection Under voltage Protection (Input Voltage <160 V), Overvoltage Protection (Input Voltage>280V), Short Circuit of UPS, Low Battery, Overload
BUYER SPECIFIC REQUIREMENT Environmental Test Report Requirements NA
Any Other Requirements As per Meity (Government of India) guidelines UPS shall have valid IS16242-Part 1 CRS certification
CERTIFICATION / TEST REPORT Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification Certificate of Govt.Lab/NABL/ILAC accredited for UPS Testing
Agree to provide all relevant documents Test Reports/supporting document /reports etc to the buyer at the time of bidding or on demand Yes