Catalogue values for Power Generator - DG Set (up to 900 KVA)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
Power Generator INSTALLATION CONFIGURATIONS | Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) | Fixed (Power Generators are permanently installed)" |
OUTPUT CAPACITY RATING/ PHASE | Nominal Rated Capacity (kVA) | 40 |
No of Phase (Single Phase-3-5kVA) (Single Phase or Three Phase-5 & 7-5, 10,15, 20, 25, 30 & 40 kVA) (Three Phase-50 to 900 kVA) | Three Phase | |
ENGINE | Rated Engine Power (kWm) | 100 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator + Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience, 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher |
Type of Engine cooling | Liquid Cooled | |
Type of governer | Electronic Or higher | |
Number of cylinders (nos) | 4, 3 | |
Rated RPM of Engine (RPM) | 1500 | |
Fuel | High Speed Diesel (HSD) | |
Starting voltage (volt) | 12 | |
Salient Features of Engine | Turbo Charged Engine, CRDi Fuel System, Ambient working temperature upto 55 degree celcius. | |
ALTERNATOR | Voltage Regulation Grade | VG 3 Or higher |
CONTROL PANEL | Control Panel | Manual Control Panel |
Control Panel Location | Inside the canopy | |
TRAILER | Trailer | Yes, NA for Fixed/Skid Mounted Power Generator |
Pay load of the Trailer | 0, 500, 1000, 2000 Or higher | |
Number of Axlels | 1, 0 | |
Number of wheels | Two wheeled, 'NA' for without trailer | |
Wheel Tyre size | 16.0, 0.0 | |
SCOPE OF INSTALLATION | Installation | Without installation, with installation - inclusive in the scope of supply Or higher |
WARRANTY/SERVICES | Warranty on Complete power genertor/DG Set | 24, 36 Or higher |
Number of preventive maintenance visits offered in an year during warranty period (Supply of all consumables is the buyer's responsibilty)* | 3, 1 | |
TEST REPORTS | Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification | Certificates required as per CPCB, Govt Lab, NABL accredited lab, NA |
Test report Available for (Test/approval) | Type Approval Certificate for the specified rating of the Power Generator from any of the designated agency authorized by CPCB, COP Certificate for engine, Type test report and Endurance test report for Engine as per IS: 10001 latest / IS: 10002 latest, Type test report for Alternator as per IS:13364 (Part-1) latest / IS:13364 (Part-2) latest to prove conformity to the specifications | |
Agree to provide all relevant documents Test Report/supporting document /reports etc to the buyer at the time of bidding or on demand | YES | |