Catalogue values for Power Generator - DG Set (up to 900 KVA)

Category Specification Bid Requirement (Allowed Values)
Power Generator INSTALLATION CONFIGURATIONS Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) Fixed (Power Generators are permanently installed)"
OUTPUT CAPACITY RATING/ PHASE Nominal Rated Capacity (kVA) 40
No of Phase (Single Phase-3-5kVA) (Single Phase or Three Phase-5 & 7-5, 10,15, 20, 25, 30 & 40 kVA) (Three Phase-50 to 900 kVA) Three Phase
ENGINE Rated Engine Power (kWm) 100 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator + Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience, 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher
Type of Engine cooling Liquid Cooled
Type of governer Electronic Or higher
Number of cylinders (nos) 4, 3
Rated RPM of Engine (RPM) 1500
Fuel High Speed Diesel (HSD)
Starting voltage (volt) 12
Salient Features of Engine Turbo Charged Engine, CRDi Fuel System, Ambient working temperature upto 55 degree celcius.
ALTERNATOR Voltage Regulation Grade VG 3 Or higher
CONTROL PANEL Control Panel Manual Control Panel
Control Panel Location Inside the canopy
TRAILER Trailer Yes, NA for Fixed/Skid Mounted Power Generator
Pay load of the Trailer 0, 500, 1000, 2000 Or higher
Number of Axlels 1, 0
Number of wheels Two wheeled, 'NA' for without trailer
Wheel Tyre size 16.0, 0.0
SCOPE OF INSTALLATION Installation Without installation, with installation - inclusive in the scope of supply Or higher
WARRANTY/SERVICES Warranty on Complete power genertor/DG Set 24, 36 Or higher
Number of preventive maintenance visits offered in an year during warranty period (Supply of all consumables is the buyer's responsibilty)* 3, 1
TEST REPORTS Type of lab which carried out Test of Complete Product to prove the conformity of product as per specification Certificates required as per CPCB, Govt Lab, NABL accredited lab, NA
Test report Available for (Test/approval) Type Approval Certificate for the specified rating of the Power Generator from any of the designated agency authorized by CPCB, COP Certificate for engine, Type test report and Endurance test report for Engine as per IS: 10001 latest / IS: 10002 latest, Type test report for Alternator as per IS:13364 (Part-1) latest / IS:13364 (Part-2) latest to prove conformity to the specifications
Agree to provide all relevant documents Test Report/supporting document /reports etc to the buyer at the time of bidding or on demand YES