Catalogue values for Isolation Transformer
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
CONSTRUCTION | Isolation transformer suitable for installed at | Inside the Lighting Distribution Board (LDB), at Welding DB panel itself, By the side of respective LDB, By the side of respective Welding DB, Inside Neutral Grounding Cubicle |
GENERIC | Description of store | Isolation transformer for Neutral Grounding |
Rating (in KVA) | 20 | |
No. of phase (in Nos.) | 1 | |
Winding connection HV/LV | Not applicable for Isolation transformer for Neutral Grounding | |
Voltage ratio | 415/415V, +/- 5% taps (OCTC) in steps of 2.5% | |
Insulation class | F | |
One minute power frequency withstand voltage (in KV) | 2.5 | |
Material of enclosure | Not applicable for Isolation transformer for Neutral Grounding | |
Enclosure protection (IP Rating), Ref. IS/IEC:60947 latest | Not applicable for Isolation transformer for Neutral Grounding | |
Enclosure protection transformer terminal box (IP Rating), Ref. IS/IEC:60947 latest | Not applicable for Isolation transformer for Neutral Grounding | |
FITTINGS FOR EACH TRANSFORMER | Number of Termination insulators (hint: If not applicable select "0") | 0 |
Number of Winding temperature indicator (s) with alarm and trip contact (as applicable) (hint: If not applicable selet "0") | 0 | |
Number of Cover lifting eyes (hint: If not applicable select "0") | 0 | |
Number of Transformer lifting lugs (hint: If not applicable select "0") | 0 | |
Number of Core and winding lifting lugs (hint: If not applicable select "0") | 0 | |
Number of Earthing terminals (hint: If not applicable select "0") | 0 | |
Number of Cable boxes (hint: If not applicable write "0") | 0 | |
Number of Tap changing links | Not applicable | |
Other requirements for each transformer | Supporting structure, Foundation Bolts, Rating and diagram plate, Towing holes | |
TESTS | Agreed to furnish additional routine test reports for | Insulation resistance, Iron loss, Paint shade, thickness/adhesion, Enclosure sheet thickness, Not applicable |
Agreed to furnish special test reports to buyer /consignee on demand | Not applicable | |
Agreed for stage inspection as and when required by buyer / consingee | Insulation resistance,Iron loss,Paint shade, thickness/adhesion,Enclosure sheet thickness | |
CERTIFICATIONS | Agreed to furnish Guaranteed Technical Particulars (GTP) and complete drawings of Transformer as and when required by buyer / consignee | Yes |
Availability of Type test reports to prove conformity of the specification | NABL AccreditedLab | |