Catalogue values for Isolation Transformer

Category Specification Bid Requirement (Allowed Values)
CONSTRUCTION Isolation transformer suitable for installed at Inside the Lighting Distribution Board (LDB), at Welding DB panel itself, By the side of respective LDB, By the side of respective Welding DB, Inside Neutral Grounding Cubicle
GENERIC Description of store Isolation transformer for Neutral Grounding
Rating (in KVA) 20
No. of phase (in Nos.) 1
Winding connection HV/LV Not applicable for Isolation transformer for Neutral Grounding
Voltage ratio 415/415V, +/- 5% taps (OCTC) in steps of 2.5%
Insulation class F
One minute power frequency withstand voltage (in KV) 2.5
Material of enclosure Not applicable for Isolation transformer for Neutral Grounding
Enclosure protection (IP Rating), Ref. IS/IEC:60947 latest Not applicable for Isolation transformer for Neutral Grounding
Enclosure protection transformer terminal box (IP Rating), Ref. IS/IEC:60947 latest Not applicable for Isolation transformer for Neutral Grounding
FITTINGS FOR EACH TRANSFORMER Number of Termination insulators (hint: If not applicable select "0") 0
Number of Winding temperature indicator (s) with alarm and trip contact (as applicable) (hint: If not applicable selet "0") 0
Number of Cover lifting eyes (hint: If not applicable select "0") 0
Number of Transformer lifting lugs (hint: If not applicable select "0") 0
Number of Core and winding lifting lugs (hint: If not applicable select "0") 0
Number of Earthing terminals (hint: If not applicable select "0") 0
Number of Cable boxes (hint: If not applicable write "0") 0
Number of Tap changing links Not applicable
Other requirements for each transformer Supporting structure, Foundation Bolts, Rating and diagram plate, Towing holes
TESTS Agreed to furnish additional routine test reports for Insulation resistance, Iron loss, Paint shade, thickness/adhesion, Enclosure sheet thickness, Not applicable
Agreed to furnish special test reports to buyer /consignee on demand Not applicable
Agreed for stage inspection as and when required by buyer / consingee Insulation resistance,Iron loss,Paint shade, thickness/adhesion,Enclosure sheet thickness
CERTIFICATIONS Agreed to furnish Guaranteed Technical Particulars (GTP) and complete drawings of Transformer as and when required by buyer / consignee Yes
Availability of Type test reports to prove conformity of the specification NABL AccreditedLab