Catalogue values for Online UPS (V2)
Category | Specification | Bid Requirement (Allowed Values) |
---|---|---|
Generic | Rating in KVA | 40.0 KVA |
Switching Technology | IGBT-PWM | |
Input Voltage | AC Three phase 300 V - 450V sinewave 50Hz | |
Output Voltage | AC 3 phase 415V having a variable setting the range starting from 380 volt - variable upto to 415 volt. | |
Warranty for UPS (Years) | 5 Or higher | |
Battery/Backup Bank | Battery/Backup Bank Provided with Online UPS ( Hint: In case the UPS is supplied with battery, seller shall ensure compliance to the GST Rates as per recommendations made in the 45th Meeting of GST council dated 17th Sep 2021 ) | With Battery |
Type of Battery (hint: NA in case Battery not provided) | SMF-VRLA conforming to JISC:8702(Pt.I,II&III), Stationary Lead Acid Batteries (with tubular positive plates) in monobloc container conforming to IS:13369:1992 latest | |
Backup time (Minutes) (hint: NA in case battery not provided) | 30 Minutes | |
Warranty for battery (Years) by Battery Manufucaturer/Brand hint: NA in case battery not provided | 2, 3 Or higher | |
Installation and Commissioning or Service | Installation and Commissioning ( Covered in the Scope of Supply) | Provided |
After sales service ( Turn Around Time) | Within 24 hours, Within 48 hours, Within 7 days, NA | |
Performance / Functional | Inbuilt isolation transformer | Without |
Overall Efficiency (%) | >/=94% without Inbuilt isolation transformer | |
Overload limit | 20% Overload for minimum 5 minute, 50% Overload for minimum 1 minute | |
Accessories | Accessories | Rack for Batteries |
Design / Construction | Type of Design / Construction | Floor Standing |